Chipkin.com

Our Customers Say
Join our mailing list
E-mail:
Name:
CAS Modbus RTU Parser
Have you ever needed to analyze a Modbus RTU message?

CAS Modbus RTU Parser
CAS Modbus TCP Parser
Have you ever needed to analyze a series of Modbus TCP message?

CAS Modbus TCP Parser
CAS BACnet explorer
Do you want to know more about your BACnet device on your network ?

CAS BACnet Explorer

ICSII Data Fact Sheet

Up one level

Chipkin Automation Systems has developed a FieldServer driver which communicates with Rapid Engineering's ICSII controllers. The driver can read process/status information and can send commands and setpoints. Combining this driver with any of the other FieldServer drivers allows you to easily transfer data between:

Web
  • Webserver
Building automation
  • Lonworks
  • BACnet
  • Metasys N2
Industial
  • Scada / HMI
  • Modbus (Full family of protocols)
  • Rockwell (Full family of protocols)
  • GE-Fanuc (Full family of protocols)
  • Siemen
  • Omron
  • DNP3
  • Opto22
  • Profibus
Fire Alarm Panels
  • Notifier AM200,300,400,600
  • Notifier 1010/2020
  • Simplex 4100
  • Siemens Cerberus MXL
  • Grinnell
  • Fike Cheetah
  • Vesda
HVAC Systems
  • Strane BCU and Summit
  • WorkStation
  • Alerton
  • Delta Controls
  • Andover Controls
  • Siemens
  • Honeywell and Automation Logic
  • DataAire
  • TekAir
  • York Chillers
  • McQuay
  • Carrier
Others
  • Catterpillar
  • Lutron
... Over 110 other protocols and counting



FieldServer Driver
FS8700-106
ICSII HVAC Controller Protocol

Description

This driver is used to exchange data between a FieldServer and an ICSII HVAC controller device.

The driver is a serial driver using an RS485 serial port to connect between the FieldServer and the ICSII capable device.

The driver provides client functionality.

As a client the driver can poll for data from the ICSII device as well as being able to some control points and set points. Details are provided below.

Server functionality is built into the driver but is not documented or supported. This functionality is implemented to support our ongoing QC efforts.

Fieldserver Mode Nodes Comments
Client 99 Up to 99 ICSII devices can be linked on one RS485 network. The functional specification of the EIA485 standard limits the number of nodes per segment to 32. If additional network segments are required then repeaters are required.




Formal Driver Type

  • Serial
  • Client



Compatibility Matrix


FieldServer Model Compatible with this driver
FS-x2010 Yes
FS-x2011 Yes
FS-x40 Yes



Connection Information


Connection type: EIA485
Baud Rates: Driver Supports : 110; 300; 600; 1200; 2400; 4800; 9600; 19200; 28800; 38400; 57600; 115200 Baud
Vendor Equipment support 9600 Baud
Data Bits: Driver Supports : 7,8
Stop Bits: Driver Supports : 1,2
Parity: Driver Supports : Odd, Even, None
Hardware interface: N/A
Multidrop Capability Yes



Devices Tested


Device Tested (FACTORY, SITE)
Call Chipkin Automation Systems for an update on this information. This driver has been tested at Chipkin Automation Systems (an approved FieldServer Integrator) using an ICSII controller during July 2004. It was subsequently tested in Beta form by a customer connected to a network of ICSII controllers during August 2004.



Connection Configurations





Connection Notes





Communications Functions - Supported functions at a glance:


Read/Write Operations supported


Cmd # FieldServer as a Client
1 Heater Status Report (Read command)
2 Setpoints Report (Read command)
3 Occupied Schedule for Air handler (Read Command)
4 Aux. Output Schedule Report. (Read Command)
5 Setpoint Range Report (Read Command)
6 Error and Reset (Read / Write command)
7 Last Power UP and Energy Info Report (Read Command)
8 Change Mode ( Write Command)
9 Change Setpoint (Write Command)
10 Change Schedule for Air handler (Write command)
20 Change Schedule for Aux Output (Write command)
11 Zero Energy Counters ( Write Command)
13 Aux Output control definition / setpoint (Write command0
12 Version Info & Config ( Read Command)



Unsupported Functions and Data Types


Cmd # Description
Uni#1 Universal Command to Change Date, time (Write Command)



Data Points


The FieldServer reads data from the ICSII device. The data points below are the points available to the FieldServer but this does not necessarily mean that they are valid for the HVAC device connected to the ICSII.


Description Category R/W
day of week Heater Status Info R
date (MMDDYY) Heater Status Info R
(HHMM) Heater Status Info R
mode Heater Status Info R
current state Heater Status Info R
current space temp setpoint Heater Status Info R
space temp times 10 Heater Status Info R
discharge temp Heater Status Info R
outside air temp Heater Status Info R
pressure setpoint times 1000 Heater Status Info R
pressure times 1000 Heater Status Info R
outside air damper Heater Status Info R
return air damper Heater Status Info R
inputs (hex) Heater Status Info R
outputs (hex) Heater Status Info R
current error Heater Status Info R
space relative humidity Heater Status Info R
valve position Heater Status Info R
future Heater Status Info R
future Heater Status Info R
occupied temperature Setpoints Info RW
unoccupied temperature Setpoints Info RW
maximum discharge temperature Setpoints Info RW
minimum discharge temperature Setpoints Info RW
building pressure times 100 Setpoints Info RW
occupied burner turnoff times Setpoints Info RW
unoccupied heater turnoff times Setpoints Info RW
occupied open relief times Setpoints Info RW
unoccupied open relief times Setpoints Info RW
low temperature shutdown Setpoints Info RW
percent outside air Setpoints Info RW
burner turnoff setpoint enable/disable(1=Enable) Setpoints Info RW
outside air temp. control enable/disable(1=Enable) Setpoints Info RW
room relative humidity setpoint Setpoints Info RW
dry-bulb enonomizer setpoint Setpoints Info RW
econ type (0,1,2) none, dry-bulb, enthalpy Setpoints Info RW
future Setpoints Info RW
future Setpoints Info RW
period(1,5,9,13,17 ), start (XXXXX = DHHMM) Occupied Schedule for Air Handler RW
period(1,5,9,13,17 ), stop (XXXXX = DHHMM) Occupied Schedule for Air Handler RW
period(2,6,10,14,18), start (XXXXX = DHHMM) Occupied Schedule for Air Handler RW
period(2,6,10,14,18), stop (XXXXX = DHHMM) Occupied Schedule for Air Handler RW
period(3,7,11,15,19), start (XXXXX = DHHMM) Occupied Schedule for Air Handler RW
period(3,7,11,15,19), stop (XXXXX = DHHMM) Occupied Schedule for Air Handler RW
period(4,8,12,16,20), start (XXXXX = DHHMM) Occupied Schedule for Air Handler RW
period(4,8,12,16,20), stop (XXXXX = DHHMM) Occupied Schedule for Air Handler RW
period(na,na,na,na,21), start (XXXXX = DHHMM) Occupied Schedule for Air Handler RW
period(na,na,na,na,21), stop (XXXXX = DHHMM) Occupied Schedule for Air Handler RW
period(1,5,9,13,17 ), start (XXXXX = DHHMM) Aux Output Schedule RW
period(1,5,9,13,17 ), stop (XXXXX = DHHMM) Aux Output Schedule RW
period(2,6,10,14,18), start (XXXXX = DHHMM) Aux Output Schedule RW
period(2,6,10,14,18), stop (XXXXX = DHHMM) Aux Output Schedule RW
period(3,7,11,15,19), start (XXXXX = DHHMM) Aux Output Schedule RW
period(3,7,11,15,19), stop (XXXXX = DHHMM) Aux Output Schedule RW
period(4,8,12,16,20), start (XXXXX = DHHMM) Aux Output Schedule RW
period(4,8,12,16,20), stop (XXXXX = DHHMM) Aux Output Schedule RW
period(na,na,na,na,21), start (XXXXX = DHHMM) Aux Output Schedule RW
period(na,na,na,na,21), stop (XXXXX = DHHMM) Aux Output Schedule RW
occupied temperature, minimum maximum Setpoint Ranges R
unoccupied temperature, minimum maximum Setpoint Ranges R
maximum discharge temperature, minimum maximum Setpoint Ranges R
minimum discharge temperature, minimum maximum Setpoint Ranges R
building pressure, minimum maximum Setpoint Ranges R
occupied burner turnoff, minimum maximum Setpoint Ranges R
unoccupied heater turnoff, minimum maximum Setpoint Ranges R
occupied open relief, minimum maximum Setpoint Ranges R
unoccupied open relief, minimum maximum Setpoint Ranges R
low temperature shutdown, minimum maximum Setpoint Ranges R
percent outside air, minimum maximum Setpoint Ranges R
error log no. 1, error no., MMDDYY, HHMM Error Info R
error log no. 2, error no., MMDDYY, HHMM Error Info R
error log no. 3, error no., MMDDYY, HHMM Error Info R
error log no. 4, error no., MMDDYY, HHMM Error Info R
last power up date (MMDDYY) Last Power UP and Energy Info R
last power up time (HHMM) Last Power UP and Energy Info R
number of power ups Last Power UP and Energy Info R
number of fan starts Last Power UP and Energy Info R
cumulative fan hours on, thousands Last Power UP and Energy Info R
cumulative fan hours on, 0-999 Last Power UP and Energy Info R
CCF - thousands Last Power UP and Energy Info R
CCF - 0-999 Last Power UP and Energy Info R
CCFH - low rate * 100 (CCF) Last Power UP and Energy Info R
CCFH - min rate * 100 (CCF) Last Power UP and Energy Info R
CCFH - max rate * 100 <- NOTE: *100 (CCF) Last Power UP and Energy Info R
CCFH - high rate * 100 <- NOTE: *100 (CCF) Last Power UP and Energy Info R
CCFH - current rate (same as 9-12 ??) Last Power UP and Energy Info R
Reset Fan Energy Counter Reset Energy Counters W
Reset Gas Energy counter Reset Energy Counters W
Control Type Aux output control Settings W
Sub Type Aux output control Settings W
Level Aux output control Settings W
 
0.022229