FieldServer Driver - Serial
FS-8700-84
Lutron eLumen
Driver Description
The Serial eLumen driver allows the FieldServer to transfer data to and from devices over RS-232 or RS-485 using eLumen protocol. The FieldServer can only be used operationally as a Lutron client driver. Any existing Lutron server drivers are for FieldServer testing purposes only and cannot be used to emulate an eLumen system.
The driver supports the following 3 panels: GRAFIK5000, GRAFIK6000 and GRAFIK7000
The hardware for all 3 panels is identical. The only differences are limits in the database. GRAFIK5000 has only 1 CSD link and can have a max of 128 zones. GRAFIK6000 has 3 CSD links with 512 zones. GRAFIK7000 has 6 links with 512 zones and can communicate with other processors.
The FieldServer eLumen driver implements the following functionality:
- Status monitoring of eLumen system data and parameters.
- System Control of eLumen.
Status monitoring is achieved by sending status requests to the eLumen system. Retrieved status data are collected and stored in FieldServer data arrays that allow access by other protocols.
System Control Commands can be configured in the FieldServer to address any groups of Areas, Zones or Scenes. A mechanism is provided by which the parameters are set before the command is triggered using the upstream protocol. Commands are provided to read the names of Areas, Zones and Scenes from the eLumen to facilitate access by SCADA systems.
| Fieldserver Mode | Nodes | Comments |
| Client | 1 | Only 1 client node allowed on Multidrop systems |
| Server |
Formal Driver Type
Serial
Client only.
Connection Information
| Connection type: | RS-232 or RS-485 (Two wire, Half-Duplex) |
| Baud Rates: | 2400; 9600; 19200; 38400 - Vendor limitation |
| Data Bits: | 8 |
| Stop Bits: | 1 |
| Parity: | None |
| Multidrop Capability: | Yes |
Compatibility Matrix
| FieldServer Model | Compatible with this driver |
| FS-B2010 | Yes |
| FS-B2011 | Yes |
| FS-B40 Series | Yes |
| FS-B30 Series | No |
Proprietary Physical Interfaces Supported
| Fieldserver Model | Adapter Model # | Vendor | Physical Medium |
Devices tested:
| Device | Tested (FACTORY, SITE) |
| Lutron Grafik6000 | Factory |
| Lutron Grafik7000 | Site |
Connection configurations
Connection Notes
Pin-out eLumen
Pin 2 Data Out
Pin 3 Data In
Pin 5 common
Communications functions - Supported functions at a glance:
Data Types Supported
Read Operations supported
| FieldServer as a client |
| Read System Names: |
|
Get Area Names Get Scene Names Get Zone Names |
| Read System Status: |
|
Get Area Status Get Timeclock Status Get Wallstation Status Get Switch Status Get Zone Intensity Get Time Now Get Astro Times Get Date Get Code Revision Level Get Boot Code Revision Level Get Serial Number Get System Variable Value Request Panel Emergency Status |
| System Zone Control: |
|
Halt Zone Toggle Zone Output Level Fade Zone to Level Ramp Up Zone Intensity Ramp Down Zone Intensity Pommel or Pulse Zone Intensity Multi Level ( Flash or Warn or Chase ) Zone Intensity Ramp Scene Zones Up Ramp Scene Zones Down Stop Scene Ramp Up Stop Scene Ramp Down |
| System Scene Control: |
|
Select System Scene Select System Scene using Override Times Output Temporary Scene Select Scene in Area |
| System Timeclock Control: |
|
Disable Until Enable Issued Disable Until End of Day or Enable Issued Re-enable with Complete Catchup Re-enable and do Previous Event Standard Re-enable New Schedule Set Timeclock |
| Wallstation Control: |
|
Enable Wallstation Disable Wallstation Simulate Wallstation Switch Press Simulate Wallstation Switch Release Run Script Set System Variable Toggle System Variable Enabling Switch Presses and Releases Reporting Disabling Switch Presses and Releases Reporting Listening to Switch Presses and Releases |
Download adobe version