FieldServer Driver - Serial
FS-8700-26
Notifier 200/300/400
| Driver Code: | NOTA |
| Version | 1.00 |
| Devices Supported: | Notifier AFP200, AFP300 and AFP400 Fire Alarm Panels |
| Interface: | RS-232 utilizing Notifier Fire Alarm Panel Connector adapter |
| Baud: | 2400 |
| Parity: | Even (AFP200); None (AFP300/AFP400) |
| Data Bits: | 7 (AFP200); 8 (AFP300/AFP400) |
| Handshaking: | None |
Device Types Supported
Detectors
Module Type Codes Supported
- Alarms
- Troubles
- Pre-Alarms
- Not Installed
- Alarms
- Troubles
- Pre-Alarms
- Not Installed
- Only if the default "Zone xx" Labeling (where xx is the zone number) is used. If custom zone descriptions are used, they will not be reported to the driver.
Module Type Codes Supported
- Monitor
- Pull Station
- Smoke Detect
- Blank
- Waterflow
- Supervisory
- Tamper
- Hazard Alert
- Fire Control
- Abort Switch
- Man-Release
- Silence
- System Reset
- Evacuate
- PAS Inhibit
- Trouble Mon
- Security
- Tele Page
- Allcall Page
- Man Rel. Delay
- Second Shot
- Sprinkler Sys
- Comb. Monitor
Note that status on control devices is not supported. As zones can be reported, this should not be a problem.