Chipkin.com

Our Customers Say
Join our mailing list
E-mail:
Name:
CAS Modbus RTU Parser
Have you ever needed to analyze a Modbus RTU message?

CAS Modbus RTU Parser
CAS Modbus TCP Parser
Have you ever needed to analyze a series of Modbus TCP message?

CAS Modbus TCP Parser
CAS BACnet explorer
Do you want to know more about your BACnet device on your network ?

CAS BACnet Explorer

FieldServer Driver - Serial
FS-8700-19
Metasys N2

Description

The Metasys N2 network supports communications with a diverse range of devices. Many N2 compatible devices use their own flavor of the protocol. The different flavors are designed to co-exist on the same N2 network. Care must be taken to ensure the device of interest is covered by the FieldServer implementation.

At present the FieldServer Metasys N2 driver will support communications with the following devices or classes of devices when acting as a client:

  1. N2Open-compliant devices. N2Open is a published N2-compatible protocol enabling 3rd party device vendors to integrate with N2.
  2. VMA 1400 series (with restrictions, see below)
  3. DX9100 and XT9100

When acting as a server the FieldServer Metasys N2 driver can emulate an N2Open device only.

Fieldserver Mode Nodes Comments
Client1 Only 1 client node allowed on Multidrop systems. Can communicate with:
  • N2Open
  • VMA 1400 series (AI,BI,AO,BO and custom types)
  • DX9100 / XT9100
Server255Number of nodes limited by N2 address space. Can only act as a N2Open server node.

Formal Driver Type

  • Serial
  • Client or Server

Connection Information

Connection type: RS-485 (Two wire, Half-Duplex)
Baud Rates: 9600 (N2 standard)
Data Bits: 8
Stop Bits: 1
Parity: None
Multidrop Capability: Yes

Devices tested

Device Supported Tested (FACTORY, SITE) N2Open Device
UNT Site
VMA1410, VMA1420 Factory and Site  
DX9100 with XT9100 extension Factory and Site  
LCP/DX9100 not tested  
NCM (FieldServer as N2Open server) Factory and Site
VAV Site
AHU not tested
VND not tested
PHX Consult Factorynot testedConsult Factory
MIG Consult Factorynot testedConsult Factory
ILC Consult Factorynot testedConsult Factory
IFC Consult Factorynot testedConsult Factory
TC-9100 Consult Factorynot testedConsult Factory
TEC1000 Consult Factorynot testedConsult Factory

Connection configurations

Connection Notes

Only one N2 client may be connected to a N2 network. If the FieldServer is to act as a client, ensure no other clients are connected to the same N2 network. In the Interceptor Mode the FieldServer can be installed between an existing N2 host and the remainder of the N2 network. It will then intercept the data, and is also able to interleave its own polls for data items not configured in the host in the time between polls sent by the host

Communications functions - Supported functions at a glance:

Function Codes Supported - N2Open:

FieldServer Data Type Description (or Device Data Type)
Analog_Input Analog Input (AI)
Digital_Input Binary Input (BI)
Analog_Output Analog Output (AO)
Digital_Output Binary Output (BO)
Float_Reg Internal Float value (ADF)
Integer Internal Integer value (ADI)
Byte Internal Byte value (BD)

Read Operations Supported - N2Open

FieldServer as a Client FieldServer as a Server
Read Current Value (all data types) Read Current Value (all data types)
direct read, Change-of-State (COS) poll direct read, Change-of-State (COS) poll
Read Attribute (all data types): Read Attribute (all data types):
direct read, specifying a legal attribute number direct read, specifying a legal attribute number direct read, specifying a legal attribute number
  Identify Self command

Write (Control) Operations Supported - N2Open

FieldServer as a Client FieldServer as a Server
Override Current Value (all data types) implemented as Write on FieldServer Override Current Value (all data types) implemented as Write on FieldServer
Override Release (all data types) Override Release (all data types)
Write Attribute (all data types) direct write, specifying a legal attribute number Write Attribute (all data types) direct write, specifying a legal attribute number

Listing of Supported Attributes - N2Open

Data Type Attribute No. Attribute
Analog Input 1 Object Configuration
2 Object Status
3 Analog Input Value
4 Low Alarm Limit
5 High Alarm Limit
6 Low Warn Limit
7 High Warn Limit
8 Differential
Binary Input 1 Object Configuration
2 Object Status
Analog Output 1 Object Configuration
2 Object Status
3 Current Value
Binary Output 1 Object Configuration
2 Object Status
3 Minimum On-Time
4 Minimum Off-Time
5 Maximum Cycles/Hour
Internal Float 1 Object Status
2 Current Value
Internal Integer 1 Object Status
2 Current Value
Internal Byte 1 Object Status
2 Current Value

Unsupported Functions and Data Types - N2Open

Function Reason
Time Update Not required
Read Memory Diagnostics Not required
Warm Start Message Not required
Status Update Message Not required
Programming messages (upload, download) FieldServer is a data transfer device, and as such, programming messages are not required

Data Types Supported - VMA

FieldServer Data Type Description (or Device Data Type)
Analog_Input Analog Input (AI)
Digital_Input Binary Input (BI)
Analog_Output Analog Output (AO)
Digital_Output Binary Output (BO)
Float_Reg Internal Float value (ADF)
Integer Internal Integer value (ADI)
Byte Internal Byte value (BD)

Read Operations Supported - VMA

FieldServer as a Client FieldServer as a Server
Read Current Value (all data types) Not applicable
Direct Read, Change-of-State (COS) poll

Write (control) Operations Supported - VMA

FieldServer as a Client FieldServer as a Server
Write / Override Current Value (all data types) implemented as Write on FieldServer Not applicable
Override Release (AI and BI only) use writes for outputs and internal values

Unsupported Functions and Data Types - VMA

Function Reason
Programming messages (upload, download) FieldServer is a data transfer device, and as such, programming messages are not required. Note that the Interceptor Mode will not allow the field devices to be programmed through the FieldServer.

Data Types Supported - DX9100

FieldServer Data Type Description (or Device Data Type)
Not specified for DX9100 device type Supported sections of Address Map:
general control module
programmable modules 1-12
analog input modules 1-8
analog output modules 1-2
digital output modules 3-8
extension modules 1-8
time schedules 1-8
optimal start/stop modules 1-2
analog output modules 9-10
auxiliary analog output modules 11-13

Read Operations Supported - DX9100

FieldServer as a Client FieldServer as a Server
Read of all points supported Not applicable

Write (control) Operations Supported - DX9100

FieldServer as a Client FieldServer as a Server
Write of all points supported Not applicable
DX9100 may not allow writes to specific values

Unsupported Functions and Data Types - DX9100

Function Reason
Programming messages FieldServer is a data transfer device, and as such, programming messages are not required
 
0.008177